Two innovative solutions make it possible to install a lifting station without pipes above the backwater level
Texte KESSEL & Wouter Polspoel | Photos KESSEL

A wastewater lifting station traditionally requires a backwater loop above the backwater level, as well as a separate air inlet and vent pipe terminating at roof level. These requirements can entail major building works, particularly in renovation projects. KESSEL, a specialist in drainage solutions, has developed two solutions that provide both backwater protection and aeration and ventilation below the backwater level: CleverLoop and CleverVent, respectively. This allows the entire installation to remain in the plant room.
A correctly installed lifting station must prevent wastewater from entering the building if backwater rises from the sewer network. To achieve this, the discharge pipe normally forms a backwater loop that rises above the backwater level. The installation also requires a separate aeration and vent pipe terminating at roof level.
In a new building, these requirements can generally be incorporated at the design stage. The situation is different in an existing building. Penetrations through floors and the roof may require work on the load-bearing structure, as well as adjustments to sound insulation and fire safety. With CleverLoop and CleverVent, KESSEL aims to avoid these pipe runs. The manufacturer says this is a world first: for the first time, backwater protection, aeration and ventilation for a lifting station can all be provided below the backwater level.

Mechanical separation to prevent backwater
CleverLoop replaces the conventional backwater loop with a mechanical system separator installed between the discharge pipe and the collector pipe. During pumping, the water flow automatically opens the passage valve. As soon as the pump stops, the mechanical shut-off device closes automatically. If backwater rises from the sewer, a float provides an additional seal.
The system separator has a modular design. Sleeves and spigots allow it to be adapted to discharge pipes from DN 50 to DN 100 and collector pipes from DN 90 to DN 200. An integrated maintenance opening provides tool-free access to the component.

Aeration and ventilation via the collector pipe
CleverVent addresses the second pipework requirement. This valve replaces the separate aeration and vent pipe terminating at roof level. In normal operation, air exchange takes place via the collector pipe and the sewer network. If backwater occurs, rising water lifts an integrated float, closing the connection to the sewer. The system then switches mechanically to aeration and ventilation using air from the room, through an activated-carbon filter. According to KESSEL, this principle also works in the event of a power cut.
This component is also fitted directly into the collector pipe. No additional riser is therefore required, and serviceable parts, including the activated-carbon filter, remain accessible.
“With the CleverLoop system separator and the CleverVent aeration and ventilation valve, we are addressing the main challenges associated with backwater protection, aeration and ventilation, as well as installation constraints,” explains Joachim Ziob, product manager at KESSEL. He also notes that these solutions reduce installation costs by up to 70 %. CleverLoop and CleverVent therefore offer particular value in renovation projects. However, KESSEL says they are also suitable for new buildings, in both residential and commercial properties.

A comprehensive technical framework
As no specific standard yet existed for these solutions, KESSEL worked with scientific partners, testing bodies and standards organisations to develop a technical framework for their use. This work resulted in DIN SPEC 3615.
CleverLoop and CleverVent have also undergone extensive testing by TÜV Rheinland and received the “Tested by TÜV” mark. The Österreichisches Institut für Bautechnik (OIB) and Swiss certification body Qplus have also issued the relevant approvals and certifications. KESSEL supplements this documentation with a manufacturer’s declaration.
With the CleverVent aeration and ventilation valve and the CleverLoop system separator, these measures are no longer necessary: both solutions operate below the backwater level.