New standards and regulations for sustainable fire safety
Texte Stephanie Demasure | Photos Pixabay, Pexels et Freepik

Fire safety requirements in and around buildings are changing rapidly. This is driven by new construction techniques and regulations, as well as a better understanding of the risks and vulnerable areas. In this article, we look at one of the most significant developments: the gradual phase-out of fluorinated foam extinguishers.

Fluorinated firefighting foams have been the standard for fire suppression since the 1960s. Fluorinated chains therefore offer significant advantages in fire suppression. They are strong and stable, allow only limited fuel absorption and provide good foam retention. These technical properties made fluorinated components a valuable addition to firefighting foams. Unfortunately, they are also difficult to break down, as has become increasingly clear in recent years, notably from levels measured at and around the 3M site in Zwijndrecht. PFAS compounds are bioaccumulative, toxic and persistent in the environment. Long-term exposure also appears to pose risks to human health.
Europe has therefore already introduced some restrictions in recent years. PFOS was banned under European legislation on 27 June 2011, PFOA was added to the blacklist in April 2020, and C9-C14-PFCAs have also been listed as prohibited substances in legislation. These are subcategories within the PFAS group. Firefighting foams containing PFOA are no longer manufactured.

A gradual phase-out over a period of varying length
Where there is no firewater collection system on site, the use of firefighting foam containing PFAS is already prohibited. However, foam can still be used for the time being in existing mobile and fixed foam extinguishing systems. The ban will come fully into force for all applications on 4 July 2025. Once this legislation has been ratified, a phase-out period for fluorinated firefighting foams will begin. Depending on the type of site and application, this phase-out may take up to 10 years. Where on-site extinguishing is used, for example by civil fire brigades and at fire extinguisher training sites, the shortest phase-out period of 18 months applies. The longest period is reserved for Seveso companies with their own firewater facilities.
Good alternatives are now available for most applications. Bulk foam for systems and installations is, however, much more complex. Foam coverage depends on several factors, such as the characteristics of the fuel and the application method. In the short term, universal fluorine-free foams may not yet be available. The bulk foam best suited to the application should therefore be assessed to identify an appropriate fluorine-free alternative. The old foam must be removed, disposed of and destroyed at high temperatures (> 1100°C) in accordance with specific rules. Once the extinguishing and storage system has been cleaned, the new foam can be introduced. This cleaning must be carried out thoroughly to prevent contamination from residual particles and the high remediation costs that could arise in the future. Note that the extinguishing system may need to be adjusted to work with the new foam.

Portable and mobile extinguishers
Around 41 million foam extinguishers still in buildings contain fluorinated foam. They consist of 90% water and 10% foam concentrate. The good news? Until they are used, they are not a potential source of pollution. As a technical partner to businesses, you have time to manage the transition gradually. These foam extinguishers can safely remain in place and should simply be replaced with an environmentally friendly, PFAS-free device within five years, a period during which the extinguisher would in any case need to be retested or replaced. Start incorporating this change into the service you offer your customers today. Together, you can spread the costs and reduce the burden on the environment right away.